Instructions for operating diesel generators

In order to create more favorable conditions for use, Huu Toan is pleased to send you the instructions on how to start diesel generators. You can completely start and operate the diesel generators by yourself according to the instructions below.

                                   CONTENT
I. Instructions for starting Huu Toan diesel generator
Note
1. Preparation before operation
2. Starting the generator
Manual operation mode
Note
Automatic operation mode
Note
II. Instructions for stopping diesel generator
1. In case of forced emergency shutdown
2. In case of normal shutdown
Note
 

Máy phát điện Hữu Toàn

I. Instructions for starting Huu Toan diesel generator

Note:

  • Before starting the generator, you need to understand the operation procedure.
  • To ensure efficient and safe operation as well as prolong the life of the generator. The customer is required to operate the generator according to the technical procedure below.

1. Preparation before operation

Before starting the generator, it is necessary to check all the items below:

  • Check the lubrication level, coolant level, and fuel level.
  • Check battery power: acid water level, battery voltage, and check battery pile tightening. Carefully connect the correct polarity.
  • Open the fuel supply valve (if any).
  • Hand lubricated oil pump for the motor (if any).
  • Check the "Emergency Stop" button is in the open position.
  • Make sure there are no objects obstructing the inside of the machine or flammable substances around the machine.

 

Máy phát điện Hữu Toàn

2. Starting the generator

Step 1: Make sure all the steps for preparation are complete.

Step 2: Start.

Manual operation mode
Double-check that the requirements in item 1 are set up properly before starting the generator.

  • Switch the power key to the "ON" position.
  • Press the initialize button to clear the current errors (if any).
  • Press the manual operation mode button.
  • Press the start button.
  • Check the parameters on the controller board.
  • Switch the source MCCB to on (ON).
  • Complete the booting process

* Note: If the ATS system is used in combination, the operator must change the ATS to the corresponding operation mode.

Automatic operation mode

  • Switch the power key to the "ON" position.
  • Press the initialize button to clear the current errors (if any).
  • Press the manual operation mode button.
  • Switch the source MCCB to on (ON).
  • Complete the booting process

* Note: If the ATS system in combination, the operator must change the ATS to the corresponding operation mode. The machine will automatically start, switch power, stop the machine depending on the status of the power source.

 

Máy phát điện Hữu Toàn

 

II. Instructions for stopping diesel generator

1. In case of forced emergency shutdown

When there is an emergency, pressing the “EMERGENCY STOP” button will stop immediately.

2. In case of normal shutdown

  • Offloading (starting with small ones first).
  • Return the source MCCB to the cut off position (OFF).
  • Idling for 2.5 minutes to cool the engine.
  • Check that the cooling water temperature must be <= 85 degrees C.
  • Press the stop button.
  • Turn the power switch to the OFF position.
  • Complete the shutdown process.

* Note: To ventilate the generator after stopping, close the other fuel valves (if any). You may open the door to cool the generator better.

For further assistance on how to operate the generator please contact our free 24/7 hotline 1800 1757.